Software Bug Contributed to Blackout

SecurityFocus: "A previously-unknown software flaw in a widely-deployed General Electric energy management system contributed to the devastating scope of the August 14th northeastern U.S. blackout, industry officials revealed this week.

The bug in GE Energy's XA/21 system was discovered in an intensive code audit conducted by GE and a contractor in the weeks following the blackout, according to FirstEnergy Corp., the Ohio utility where investigators say the blackout began. 'It had never evidenced itself until that day,' said spokesman Ralph DiNicola. 'This fault was so deeply embedded, it took them weeks of pouring through millions of lines of code and data to find it.'

The flaw was responsible for the alarm system failure at FirstEnergy's Akron, Ohio control center that was noted in a November report from the U.S.-Canadian task force investigating the blackout. The report blamed the then-unexplained computer failure for retarding FirstEnergy's ability to respond to events that lead to the outage, when quick action might have limited the blackout's spread.

'Power system operators rely heavily on audible and on-screen alarms, plus alarm logs, to reveal any significant changes in their system's conditions,' the report noted. FirstEnergy's operators 'were working under a significant handicap without these tools. However, they were in further jeopardy because they did not know that they were operating without alarms, so that they did not realize that system conditions were changing.'

The cascading blackout eventually cut off electricity to 50 million people in eight states and Canada.

The blackout occurred at a time when the Blaster computer worm was wreaking havoc across the Internet. The timing triggered some speculation that the virus may have played a role in the outage -- a theory that gained credence after SecurityFocus reported that two systems at a nuclear power plant operated by FirstEnergy had been impacted by the Slammer worm earlier in the year.

Instead, the XA/21 bug was triggered by a unique combination of events and alarm conditions on the equipment it was monitoring, DiNicola said. When a backup server kicked-in, it also failed, unable to handle the accumulation of unprocessed events that had queued up since the main system's failure. Because the system failed silently, FirstEnergy's operators were unaware for over an hour that they were looking at outdated information on the status of their portion of the power grid, according to the November report. "

Comments

Popular posts from this blog

New York Post Online Edition

news : "December 29, 2003 -- WASHINGTON - Startling new Army statistics show that strife-torn Baghdad - considered the most dangerous city in the world - now has a lower murder rate than New York. The newest numbers, released by the Army's 1st Infantry Division, reveal that over the past three months, murders and other crimes in Baghdad are decreasing dramatically and that in the month of October, there were fewer murders per capita there than the Big Apple, Chicago, Los Angeles and Washington, D.C. The Bush administration and outside experts are touting these new figures as a sign that, eight months after the fall of Saddam Hussein, major progress is starting to be made in the oft-criticized effort by the United States and coalition partners to restore order and rebuild Iraq. 'If these numbers are accurate, they show that the systems we put in place four months ago to develop a police force based on the principles of a free and democratic society are starting to

The Jodie Lane Project Responds to City Council Testimony

The Jodie Lane Project : New York, NY -- February 12, 2004. The City Council Transportation Committee held a hearing today to investigate the causes of Jodie S. Lane’s tragic electrocution death on January 16th. The testimony revealed a startling lack of oversight on the part of the Public Services Commission, charged with overseeing Con Edison’s compliance with the National Electric Safety Code, last revised in 1913. With only 5 inspectors at their disposal, the Public Services Commission relies entirely on Con Edison to report safety problems. Because Con Edison only reports incidents resulting in injury or death, the PSC was aware of only 15 shock incidents in the last 5 years. Con Edison has acknowledged that it actually received 539 reports of shock incidents in the same period, effectively admitting to misleading the PSC by an order of magnitude. It is not only this discrepancy that is alarming, but also the fact that the Public Services Commission, charged with ensuring